GE Fanuc IC694MDL645

/automation/ge-fanuc/rx3i-pacsystem/IC694MDL645

Rx3i PacSystem

Input module 24 VDC 16 point POS/NEG logic. IC694M IC694MD

IC694MDL

919-535-3180

*******************

6

Input Module, 24 Volt DC Pos/Neg, 16 Point: IC694MDL645

1 2 3 4 5 6 7 8

F

9 10 1112 13 1415 16

IC694MDL645

I1

I2

I3

I4

I5

I6

I7

I8

I9

I10

I11

I12

I13

I14

I15

I16

The 24 volt DC Positive/Negative Logic Input module,

IC694MDL645, provides 16 input points in one group with a common

power input terminal. This input module can be wired for either

positive logic or negative logic. Input characteristics are compatible

with a wide range of input devices, such as pushbuttons, limit

switches, and electronic proximity switches. Current into an input

point results in a logic 1 in the input status table (%I). Field devices

can be powered from an external supply. Depending on their

requirements, some input devices can be powered from the module’s

+24V OUT and 0V OUT terminals.

Sixteen green LEDs indicate the ON/OFF status of points 1 through

16. The blue bands on the label show that MDL645 is a low-voltage

module.

This module can be installed in any I/O slot in an RX3i system.

Specifications: MDL645

Rated Voltage

Input Voltage Range

Inputs per Module

Isolation: Field to Backplane

(optical) and to frame ground

Input Current

Input Characteristics

On–state Voltage

Off–state Voltage

On–state Current

Off–state Current

On response Time

Off response Time

Power Consumption: 5V

Power Consumption: 24V

24 volts DC

0 to +30 volts DC

16 (one group with a single

common)

250 VAC continuous;

1500 VAC for one minute

7mA (typical) at rated voltage

11.5 to 30 volts DC

0 to +5 volts DC

3.2mA minimum

1.1mA maximum

7ms typical

7ms typical

80mA (all inputs on) from 5 volt

bus on backplane

125mA from the Isolated 24 volt

backplane bus or from user

supplied power

Refer to Appendix A for product standards and general specifications

.

GFK-2314C Chapter 6 Discrete Input Modules 6-23

6

Field Wiring: MDL645

Terminals Connections

Module Circuits Terminals Field Wiring

1 Inputs 1-16 Common

2 Input 1

Other Circuits

1

3 Input 2

I1

2

4 Input 3

I2

3

5 Input 4

I3

.1µf

6 Input 5

4

680

I4

7 Input 6

5

I5

8 Input 7

6

Optical

I6

Coupler

9 Input 8

7

I7

10 Input 9

8

- +

3.3K

I8

11 Input 10

9

I9

- +

12 Input 11

10

I10

13 Input 12

11

I11

14 Input 13

12

I12

15 Input 14

13

I13

16 Input 15

14

I14

17 Input 16

15

18 24VDC for input

I15

16

devices

I16

17

19 0V for input devices

18

24V OUT

20 No connection

19

0V OUT

20

NC

Note: If the 24V OUT pin is used to connect to input devices in the field, the isolation

specification for this module changes to:

Field to Backplane (optical) and to frame ground: 50 VAC continuous; 500 VAC for 1 minute