admin管理员组文章数量:1531326
2024年7月14日发(作者:)
GE Fanuc IC694MDL645
/automation/ge-fanuc/rx3i-pacsystem/IC694MDL645
Rx3i PacSystem
Input module 24 VDC 16 point POS/NEG logic. IC694M IC694MD
IC694MDL
919-535-3180
*******************
6
Input Module, 24 Volt DC Pos/Neg, 16 Point: IC694MDL645
1 2 3 4 5 6 7 8
F
9 10 1112 13 1415 16
IC694MDL645
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
The 24 volt DC Positive/Negative Logic Input module,
IC694MDL645, provides 16 input points in one group with a common
power input terminal. This input module can be wired for either
positive logic or negative logic. Input characteristics are compatible
with a wide range of input devices, such as pushbuttons, limit
switches, and electronic proximity switches. Current into an input
point results in a logic 1 in the input status table (%I). Field devices
can be powered from an external supply. Depending on their
requirements, some input devices can be powered from the module’s
+24V OUT and 0V OUT terminals.
Sixteen green LEDs indicate the ON/OFF status of points 1 through
16. The blue bands on the label show that MDL645 is a low-voltage
module.
This module can be installed in any I/O slot in an RX3i system.
Specifications: MDL645
Rated Voltage
Input Voltage Range
Inputs per Module
Isolation: Field to Backplane
(optical) and to frame ground
Input Current
Input Characteristics
On–state Voltage
Off–state Voltage
On–state Current
Off–state Current
On response Time
Off response Time
Power Consumption: 5V
Power Consumption: 24V
24 volts DC
0 to +30 volts DC
16 (one group with a single
common)
250 VAC continuous;
1500 VAC for one minute
7mA (typical) at rated voltage
11.5 to 30 volts DC
0 to +5 volts DC
3.2mA minimum
1.1mA maximum
7ms typical
7ms typical
80mA (all inputs on) from 5 volt
bus on backplane
125mA from the Isolated 24 volt
backplane bus or from user
supplied power
Refer to Appendix A for product standards and general specifications
.
GFK-2314C Chapter 6 Discrete Input Modules 6-23
6
Field Wiring: MDL645
Terminals Connections
Module Circuits Terminals Field Wiring
1 Inputs 1-16 Common
2 Input 1
Other Circuits
1
3 Input 2
I1
2
4 Input 3
I2
3
5 Input 4
I3
.1µf
6 Input 5
4
680
I4
7 Input 6
5
I5
8 Input 7
6
Optical
I6
Coupler
9 Input 8
7
I7
10 Input 9
8
- +
3.3K
I8
11 Input 10
9
I9
- +
12 Input 11
10
I10
13 Input 12
11
I11
14 Input 13
12
I12
15 Input 14
13
I13
16 Input 15
14
I14
17 Input 16
15
18 24VDC for input
I15
16
devices
I16
17
19 0V for input devices
18
24V OUT
20 No connection
19
0V OUT
20
NC
Note: If the 24V OUT pin is used to connect to input devices in the field, the isolation
specification for this module changes to:
Field to Backplane (optical) and to frame ground: 50 VAC continuous; 500 VAC for 1 minute