admin管理员组文章数量:1531405
2024年7月14日发(作者:)
GE Fanuc IC695ALG808
/automation/ge-fanuc/rx3i-pacsystem/IC695ALG808
Rx3i PacSystem
Isolated Analog Output module, 8 channels, that is configurable IC695A
IC695AL IC695ALG
919-535-3180
*******************
GFK-2481
November 2007
MODULE OK
FIELD STATUS
TB
IC695ALG808
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
PACSystems™ RX3i
Isolated Analog Output Module, IC695ALG808
Isolated Analog Voltage/Current Output module IC695ALG808 provides
eight configurable voltage or current output channels. Analog channels can
be configured for these output ranges:
▪ Current: 0 to 20mA, 4 to 20mA
▪ Voltage: +/- 10V, 0 to 10V
The module must be located in an RX3i Universal Backplane. It requires an
RX3i CPU with firmware version 5.0 or later. Machine Edition Version 5.7
SP3 Logic Developer-PLC or later must be used for configuration.
These modules can be used with a Box-style (IC694TBB032), Extended
Box-style (IC694TBB132), Spring-style (IC694TBS032), or Extended
Spring-style (IC694TBS132) Terminal Block. Extended terminal blocks
provide the extra shroud depth needed for shielded wiring. See the
PACSystems RX3i System Manual, GFK-2314 revision B or later for more
information about Terminal Blocks. Terminal Blocks are ordered separately.
Isolated +24 VDC Power
The module must receive 24 VDC field power from an external source. The
external source must be connected directly to the module’s terminal block. It
cannot be connected via the TB1 connector on the RX3i Universal
Backplane.
Module Features
▪ Completely software-configurable, no module jumpers to set
▪ Individually enable or disable channels
▪ Clamping and Alarm Limits
▪ Latching of Alarms
▪ Configurable output bias
▪ Rapid channel acquisition times based on filter frequency
▪ On-board error-checking
▪ Configurable scaling and offsets per channel
▪ High alarm, low alarm, high-high alarm, low-low alarm detection and
reporting selectable per channel
▪ Module fault reporting
▪ Configurable Hold Last State or Output Defaults
2 RX3i Isolated Analog Output Module
GFK-2481
Specifications
Output Ranges
Backplane Power Requirements
Power Dissipation within
Module
Thermal Derating
External +Power Supply
Resolution
Output Data Format
Analog Update Rate
(Determined by I/O scan time,
application dependent)
Output Overvoltage Protection
Calibrated Accuracy
Current: 0 to 20mA, 4 to 20mA
Voltage: +/- 10V, 0 to 10V
80mA maximum at 3.3V
7.25 Watts maximum (Vuser=24V)
See derating curves later in this document
Voltage Range: 19.2V to 30V (24V nominal)
Current: 600mA maximum
+/-10V: 15.9 bits, 0 to 10V: 14.9 bits, 0 to 20mA: 15.9 bits,
4 to 20mA : 15.6 bits
Configurable as floating point IEEE 32 bit or 16-bit integer in a 32-bit field
8 milliseconds (approximate, all eight channels)
Current outputs only: -30V for 60 seconds, +30V for one hour
Accurate to within 0.15% of full scale at 25°C
Accurate to within 0. 25% of full scale at 60°C
In the presence of severe RF interference (IC 801-3, 10V/M), accuracy may
be degraded to +/-1% FS.
Current: 10µH maximum, Voltage: 1µF maximum
Current: 1350 Ohms maximum
Voltage: 2 Kohms minimum
Voltage output: 20ppm per degree C typical
Current output: 35ppm per degree C typical
Voltage or current output: 2ms, 0 to 95%
2550VDC for one second
Output Load Reactance
Maximmum Output Load
Output Gain Drift
Output Settling Time
Isolation, Field to Backplane
Output Points vs. Temperature, Current Mode
Thermal deratings for module IC695ALG808 are shown below.
RX3i Isolated Analog Output Module
3
GFK-2481
Release History
Version
IC695ALG808-AA
Firmware
Revision
1.00
Upgrade Kit
None: Initial Release
LEDs
The Module OK LED indicates module status. The Field Status LED indicates whether the external +24
VDC power supply is present and is above the minimum level and whether or not faults are present. All
LEDs are powered from the backplane power bus.
LED
Module OK
Indicates
ON Green: Module OK and configured.
Quick Flashing Green: Module performing powerup sequence.
Slow Flashing Green or Amber: Module OK but not configured.
OFF: Module is defective or no backplane power present
Field Status ON Green No faults on any enabled channel, Terminal Block is present, and field
power is present.
ON Amber and TB Green: Terminal Block is installed, fault on at least one
channel, or field power is not present.
ON Amber and TB Red: Terminal Block not fully removed, field power still
detected.
OFF and TB Red: Terminal block not present and no field power is detected.
TB ON Red: Terminal block not present or not fully seated. See above.
ON Green: Terminal block is present. See above.
OFF: No backplane power to module.
4 RX3i Isolated Analog Output Module
GFK-2481
Field Wiring
The table below lists wiring connections for the Isolated Analog Output Modules. There are no shield
terminals.
Terminal Assignment
1 No Connect
2 Channel 1 Voltage/Current Output
3 Channel 1 Ground/Return
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
No Connect
No Connect
Channel 2 Voltage/Current Output
Channel 2 Ground/Return
No Connect
No Connect
Channel 3 Voltage/Current Output
Channel 3 Ground/Return
No Connect
No Connect
Channel 4 Voltage/Current Output
Channel 4 Ground/Return
No Connect
External + Power Supply (+24V In)
External - Power Supply (+24V Rtn)
Assignment Terminal
No Connect
Channel 5 Voltage/Current Output
Channel 5 Ground/Return
No Connect
No Connect
Channel 6 Voltage/Current Output
Channel 6 Ground/Return
No Connect
No Connect
Channel 7 Voltage/Current Output
Channel 7 Ground/Return
No Connect
No Connect
Channel 8 Voltage/Current Output
Channel 8 Ground/Return
No Connect
No Connect
No Connect
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Each channel can be individually configured to operate as a voltage output or a current output - not both
simultaneously.
No Connect
1
2
3
4
5
Voltage
Output
Current
Output
19
No Connect
20
Channel 5 Output
21
Channel 5 Return
22
No Connect
23
24
Channel 1 Output
Channel 1 Return
No Connect
+
V
_
+
_
I
.
6
24VDC
+
-
17
.
.
.
18
36
There are no shield terminals on these modules. For shielding, tie cable shields to the ground bar along the
bottom of the backplane. M3 tapped holes are provided in the ground bar for this purpose.
For technical assistance, please go to /support