admin管理员组

文章数量:1531525

2024年7月14日发(作者:)

GFK-2379

March 2005

1 2 3 4 5 6 7 8

9 1011 12 1314 15 16F

17 1819 20 2122 23 24

25 2627 28 2930 31 32

TB

IC694MDL660

I1

I2

I3

I4

I5

I6

I7

I8

I9

I10

I11

I12

I13

I14

I15

I16

I17

I18

I19

I20

I21

I22

I23

I24

I25

I26

I27

I28

I29

I30

I31

I32

PACSystems™ RX3i

IC694MDL660

24VDC 32-Point Positive/Negative Logic Input Module

The 24 VDC Positive/Negative Logic Input module, IC694MDL660, provides 32

discrete input points. The inputs are positive or negative logic inputs and will operate

at levels up to 30V.

The inputs are arranged in four isolated groups of eight; each group has its own

common. Isolation is provided between the four groups of inputs, however each

group of eight inputs is referenced to the same user common connection.

Module MDL660 provides seven selectable input filter times. Filter times can be set

from the programmer using the module’s assigned output data references.

This module can be used with either a Box-style (IC694TBB032) or Spring-style

(IC694TBS032) front Terminal Block. The Terminal Block is ordered separately.

32 green LEDs indicate the ON/OFF status of points 1 through 32. The red/green

TB LED is green when the module’s removable terminal block is locked in place. It is

red when the terminal block is not locked. The module also sends an Addition of

Terminal Block or Loss of Terminal Block message to the RX3i CPU to report the

terminal block status.

The blue bands on the label show that MDL660 is a low-voltage module.

This module can be installed in any I/O slot in an RX3i system. It must be used with

an RX3i CPU (release 2.90 or greater). It cannot be used with a Series 90-30 PLC

CPU.

Module MDL660 uses 48 input bits and 16 output bits to exchange point status and

filter information with the RX3i CPU.

2 RX3i 24VDC 32-Point Positive/Negative Logic Input Module

GFK-2379

Release Information

Release History

Release Comments

IC694MDL660A Initial Release

Known Restrictions and Open Issues in this Release

1. Problem: If the module has corrupted or missing firmware (its LEDs will be OFF), it may still be scanned by the CPU,

and there may be no fault messages to indicate that the module is not operating.

Recommendation: In critical control applications, do not rely solely on diagnostic fault messaging to provide

notification of module inoperability.

2. Problem: Firmware updates may fail before they are completed, leaving the module in a “lights out” condition.

Recommendation: Cycle power to the module and try the firmware update again.

3. Problem: Rarely, hot insertion/removal of the MDL660A module triggers a Loss/Addition of Terminal Block fault

message.

Recommendation: If the terminal block is present and locked, ignore the Loss/Addition of Terminal Block fault

message.

4. Problem: Rarely, after a period of many rapidly-repeated power cycles, the module may go “lights out”.

Recommendation: Avoid multiple power cycles of periods less than 1 second. Also, avoid relay-switching of power to

PLC. (Relays can bounce creating rapid power cycling).

RX3i

24VDC 32-Point Positive/Negative Logic Input Module 3

GFK-2379

Specifications: IC694MDL660

Rated Voltage

Input Voltage Range

Inputs per Module

Isolation, Field to

Backplane (optical)

Isolation, Group to

Group

Input Current

Module ID

Input Characteristics:

On–state Voltage

Off–state Voltage

On–state Current

Off–state Current

Input Filter Times

On response Time

Off response Time

Power Consumption

Diagnostics

24 volts DC

0 to 30 volts DC

32 (four isolated groups of 8 inputs)

250 VAC continuous;

1500 VAC for one minute

250VAC continuous;

1500 VAC for one minute

7.0 mA per point (typical) at rated voltage

0x058h

11.5 to 30 VDC

0 to 5 VDC

3.2mA minimum

1.1mA maximum

0.5ms, 1.0ms, 2.0ms, 5ms, 10ms, 50ms and 100ms,

selectable per module

0.5ms, 1.0ms, 2.0ms, 5.0ms, 10.0ms, 50.0ms &

100.0ms (as per filter setting)

0.5ms, 1.0ms, 2.0ms, 5.0ms, 10.0ms, 50.0ms &

100.0ms (as per filter setting)

300mA (all inputs on) from 5 volt bus on backplane

Terminal block presence reported to RX3i CPU

4 RX3i 24VDC 32-Point Positive/Negative Logic Input Module

GFK-2379

Field Wiring: MDL660

Connections Terminals Terminals Connections

Input 1 1 19 Input 17

Input 2 2 20 Input 18

Input 3 3 21 Input 19

Input 4 4 22 Input 20

Input 5 5 23 Input 21

Input 6 6 24 Input 22

Input 7 7 25 Input 23

Input 8 8 26 Input 24

Common 1 - 8 9 27 Common 17 - 24

Input 9 10 28 Input 25

Input 10 11 29 Input 26

Input 11 12 30 Input 27

Input 12 13 31 Input 28

Input 13 14 32 Input 29

Input 14 15 33 Input 30

Input 15 16 34 Input 31

Input 16 17 35 Input 32

Common 9 - 16 18 36 Common 25 - 32

Field Wiring Terminals Field Wiring

Input 1

Input 2

Input 3

Input 4

Input 5

Input 6

Input 7

Input 8

1

2

3

4

5

6

7

8

9

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

Input 17

Input 18

Input 19

Input 20

Input 21

Input 22

Input 23

Input 24

Input 9

Input 10

Input 11

Input 12

Input 13

Input 14

Input 15

Input 16

10

11

12

13

14

15

16

17

18

Input 25

Input 26

Input 27

Input 28

Input 29

Input 30

Input 31

Input 32

本文标签: 逻辑正负